Transformer (bushing) frequency domain dielectric loss detector SAC10000
1. Product Appearance

2. Product Characteristics Advantages and Applications
(1) The high-voltage amplifier can measure capacitance and dielectric loss at 10kV voltage, improving anti-interference ability
(2) Wide frequency range measurement, DC to 1kHz, improves moisture detection sensitivity
(3) Direct testing, no need to sample the transformer, more convenient and quicker
(4)Automatically calibrate the phase angle in different environments to improve test accuracy
(5)Establish multiple pattern libraries to improve the accuracy of defect diagnosis of the equipment under test
3. Application
Mainly used for capacitance and introduction testing of high voltage equipment:
Power transformer (bushing)
Transformer
Generators and Engines
Insulating oil
4. Technical Parameters
name |
Parameters |
High voltage amplifier output voltage |
10kV |
Frequency output range |
0.001Hz-1kHz |
High voltage amplifier maximum output current |
40mA |
Dielectric loss measurement range |
0-10 |
Capacitance measurement range |
10pF-100uF |
Measurement error |
<0.5% |
Programmable output voltage |
DC-10V peak |
Programmable output current |
DC-50mA peak |
Wiring method |
Positive or negative wiring |
Software Algorithm |
Supporting insulation status diagnosis algorithm |
Operating temperature |
-10℃ to +50℃ |
Storage temperature |
-20℃ to +70℃ |
Relative humidity |
<90%RH, non-condensing |
Communication |
Network port |
EMC level |
GB17626, Level 4 |
Power supply mode |
AC220V |