941-HPD-4200 Cable High Frequency Partial Discharge Diagnostic Instrument

Item No.: 941
HPD-4200 is a high-end expert detection system independently developed by our company for power cables, which integrates high-frequency partial discharge detection, anti-interference and diagnosis. It has high sensitivity, wide frequency domain, high accu
Description

HPD-4200 Cable High Frequency Partial Discharge Diagnostic Instrument

1. System Introduction
HPD-4200 is a high-end expert detection system independently developed by our company for power cables, which integrates high-frequency partial discharge detection, anti-interference and diagnosis. It has high sensitivity, wide frequency domain, high accuracy and excellent anti-interference performance. The product is positioned for sparse discharge signal detection and fast fault phasing of three-phase split cables in complex interference environments on site.
Product images:

2. Anti-interference and fault phasing technology
HPD-4200 integrates our company's independent intellectual property rights of system interference suppression strategy and fault phasing technology. Embedded real-time frequency domain filtering technology is used to deal with narrowband or white noise interference; multi-source clustering separation technology is used to deal with stubborn pulse interference; multi-channel polarity analysis and amplitude distribution comparison technology is used to deal with crosstalk and fault phasing between phases.

See the original picture for anti-interference  1.vsdx
3. Accurate identification of discharge defect types
Taking into full consideration typical internal defect modes of power cables, a rich expert sample library was built by combining laboratory and field data. A variety of pattern recognition methods were used for hierarchical identification and comprehensive diagnosis to continuously optimize the recognition accuracy of discharge types.
Diagnosis type map:


4. Excellent system performance
name Parameters
Number of channels 4 channels
Detection frequency band 100KHz-100MHz
Sensitivity ≤5pC (Laboratory)
Sampling rate 100MSa/s
Dynamic Range ≥60dB
Smart Diagnosis Accuracy > 80%
Synchronous mode Internal synchronization: 50Hz
External synchronization: 20~300Hz
Spectrum PRPD, PRPS, time-frequency spectrum, phase-specific clustering spectrum, etc.
Anti-interference Multi-band bandpass filtering technology
Single channel time-frequency clustering technology
Three-phase polarity identification analysis technology
Three-phase amplitude clustering and phasing techniques
Communication Optical fiber, network cable
EMC level GB17626, Level 4
Power supply mode Rechargeable battery, power supply time ≥ 8 hours
sensor Transmission impedance ≥15mV/mA@50Ω impedance matching